- 20
- Apr
Environmental requirements for high-frequency equipment: (operating conditions)
Environmental requirements for high-frequency equipment: (operating conditions)
1) Surrounding environment
a. The altitude does not exceed 1000m;
b. The ambient temperature is between 5°C and 40°C;
c. The relative humidity is not more than 90% (25°C);
d. There is no conductive dust, explosive gas and corrosive gas that can seriously damage metal and insulation around;
e. There is no obvious vibration and bump.
2) Power supply requirements
a. The three-phase unbalance degree of grid voltage is not more than 5%;
b. Grid voltage fluctuation is not greater than ±10%;
c. The grid voltage must be a sine wave, and the fluctuation of the waveform must not exceed 10%.
3) Cooling water requirements
Water quality: a, total hardness < ph8.5
b. Dissolved solids < 200mg / 1
c. PH value 7 ~ 8.5
d. Suspended solids < 10mg / 1
e. Conductivity < 500S/cm
Water supply system: a. Water inlet pressure 0.15Mpa-0.3Mpa
b. Inlet water temperature 5℃~25℃
c. Outlet water temperature ≤ 40°C