site logo

1 ton induction melting furnace transformer selection case

1 ton induction melting furnace transformer selection case

To configure an ordinary transformer, you should choose 800KVA or 1000KVA rectifier transformer

Melting time: 45 minutes

Melting capacity: 1.1T

Main technical parameters of transformer

1.1 Specification model: ZSS11 (12-pulse transformer)

1.2 Rated capacity: 500KVA

1.3 Rated voltage of high voltage side: 10KV current: 57.7A

1.4 Rated voltage of low voltage side: 0.575KV×2 Current: 502A×2

1.5 No-load loss: 680W No-load current: 1.0%

1.6 Load loss: 5150W short circuit impedance: 4.5%

1.7 Cooling method: natural cooling

1.8 Transformer installation location: outdoor

1.9 Number of phases: three phases

2.0 rated frequency: 50HZ

2.1 Connection group: D.yn11-d0 Collapse d

https://songdaokeji.cn/category/products/induction-melting-furnace

https://songdaokeji.cn/category/blog/induction-melting-furnace-related-information

firstfurnace@gmil.com

Утас: 8618037961302