Sebab-sebab kegagalan tekanan tinggi penyejuk adalah seperti berikut
The reasons for the high-pressure failure of the chiller are as follows:
(1) The cooling water temperature is too high and the condensation effect is poor. The rated working condition of the cooling water required by the chiller is 30~35℃. High water temperature and poor heat dissipation will inevitably lead to high condensing pressure. This phenomenon often occurs in high temperature seasons. The reason for the high water temperature of the chiller may be: cooling tower failure, such as the fan is not turned on or even reversed, the water distributor does not turn, it is manifested as the cooling water temperature is very high, and the chiller rises rapidly; the outside air temperature is high, the water path is short, The amount of water that can be circulated by the chiller is small. In this case, the temperature of the cooling water is generally maintained at a relatively high level. The chiller can be solved by increasing the storage tank.
(2) Aliran air penyejuk tidak mencukupi dan tidak boleh mencapai aliran air terkadar. Prestasi utama penyejuk ialah perbezaan tekanan antara air masuk dan keluar unit menjadi lebih kecil (berbanding dengan perbezaan tekanan pada permulaan sistem mula beroperasi), dan perbezaan suhu menjadi lebih besar. Sebab aliran air tidak mencukupi adalah kekurangan air dalam sistem atau kehadiran udara. Penyelesaiannya ialah memasang injap ekzos pada ketinggian saluran paip untuk ekzos; penapis saluran paip disekat atau pemilihan terlalu halus, dan kebolehtelapan air adalah terhad. Penyejuk air harus memilih penapis yang sesuai Dan bersihkan penapis dengan kerap; pam air kecil dan tidak sepadan dengan sistem