site logo

औद्योगिक रेफ्रिजरेटर प्रणाली में गैर-संघननीय गैस का गठन क्या होता है?

औद्योगिक रेफ्रिजरेटर प्रणाली में गैर-संघननीय गैस का गठन क्या होता है?

In the condenser of the refrigeration system, some non-condensable gas is often collected. This kind of non-condensable gas appreciates the heat transfer of the induction condenser, increases the condensation pressure and the condensation temperature and pressure, thereby increasing the power consumption of the induction compressor. Air-cooled chiller

The non-condensable gas in the industrial refrigerator system is mainly composed of atmosphere. The atmosphere and other non-condensable gases in the industrial refrigerator make the condensation pressure of the system too high.

The atmosphere comes in the first pass of the freezer system

1. There is a residual atmosphere in the system before the first refrigerant charge

2. When the evaporating pressure is lower than atmospheric pressure, the atmosphere will enter the system through the setting and valve gaskets. 3. When the freezer is opened for maintenance, washing or additional installation, the atmosphere will enter the system

4. When the freezer is supplied with refrigerant and brake oil, the atmosphere will enter the system

5. The decomposition of refrigerant or lubricating oil will produce non-condensable gas.

वायुमण्डल तथा असंघनित गैस को समाप्त करने का उपाय है

1. संचायक का डिस्चार्ज वाल्व बंद करें और फिर कंप्रेसर चालू करें। सिस्टम में रेफ्रिजरेंट के संचयक में डिस्चार्ज होने के बाद, मशीन को बंद कर दें। जब कंप्रेसर चल रहा हो, तो अत्यधिक स्राव दबाव से बचने के लिए हर समय प्रेशर गेज पर ध्यान दें।

2. After the compressor stops, continue to pass cooling water to the condenser and pay attention to the temperature of the inlet and outlet water. After about an hour, when the inlet and outlet water temperatures of the cooling bearing are the same, check the pressure of the condenser and the saturation pressure of the refrigerant used at that temperature (water overflow) (you can find it from the thermodynamic nature table of the refrigerant, Note that the thermal nature table usually provides full pressure values). If it is too high, the slow steamer will open the top of the condenser to release the atmosphere and secrete the atmosphere and non-condensable gas.

3. वायुमंडल का निर्वहन करते समय, दबाव नापने का यंत्र द्वारा प्रदर्शित दबाव परिवर्तन का निरीक्षण करें और सर्द के नुकसान से बचने के लिए, डिस्चार्ज की गई गैस की सांस को अलग करने पर ध्यान दें। वायुमंडल वाल्व खोलने से पहले, कंडेनसर को पूरी तरह से ठंडा करना और उसके दबाव को यथासंभव कम करना आवश्यक है।

जब कम तापमान वाले रेफ्रिजरेटर सिस्टम में वातावरण मिलाया जाता है, तो वातावरण रेफ्रिजरेंट की तरफ हीट ट्रांसफर ट्यूब पर जमा हो जाएगा। वातावरण के उच्च तापीय प्रतिरोध को देखते हुए, संक्षेपण क्षेत्र पर्याप्त नहीं है, और सर्द के संघनन तापमान का संघनन दबाव बढ़ जाता है।