site logo

Các phương pháp phát hiện rò rỉ kiểm tra áp suất cho hệ thống làm lạnh trục vít là gì?

What are the pressure test leak detection methods for máy làm lạnh trục vít hệ thống lạnh?

1. Close the discharge valve of the compressor, open all other valves in the system (such as the discharge valve of the liquid reservoir, expansion valve, etc.), unscrew the tapered plug on the discharge valve, and connect the corresponding discharge valve. trachea.

2. After the system is properly adjusted, start the compressor. The preparation before starting the compressor is the same as that of the ammonia compressor.

3. The compressor can be performed intermittently during vacuuming, but the oil pressure of the compressor should be 200 mmHg higher than the suction pressure. If the oil pressure relay is installed, the contacts of the oil pressure relay should be temporarily kept in the normal state, otherwise, the pressure will be lower than the setting value of the oil pressure relay, the compressor will stop automatically, which will affect the vacuuming work.

4. Khi áp suất bơm lên 650 mmHg thì máy nén không thể xả khí. Lỗ vít côn của van xả có thể được chặn bằng tay, và có thể nhanh chóng mở van xả của máy nén để đóng chặt thiết bị ngắt van. Nới lỏng tay và vặn vào phích cắm của vít côn. Và dừng hoạt động của máy nén.

5. Sau khi hệ thống được hút chân không, để yên trong 24 giờ, và máy đo chân không đạt tiêu chuẩn nếu nó không tăng quá 5 mmHg.