Performance parameter table of epoxy glass fiber wound insulation cylinder

Performance parameter table of epoxy glass fiber wound insulation cylinder

Product use: Widely used in the main insulators of high-voltage products such as oil-immersed transformers, H-class dry-type transformers, railway locomotive transformers, on-load tap-changers, reactors, arresters, SF6 transformers, and test devices.

المميزات:

1. High withstand voltage

2. خسارة عازلة منخفضة

3. The partial discharge is small

4. قوة ميكانيكية عالية

5. No deformation and no delamination

6. امتصاص الماء منخفض جدا

7. Chemical resistance (SF6 resistance)

Product specifications: the inner diameter of the insulating cylinder ranges from Φ6mm to Φ2480mm, the wall thickness of the small tube is ≥0.5mm, the wall thickness of the large tube is ≥3mm, the wall thickness of the super-large tube is ≥5mm, and the length is within the length of the core mold. Our company has more than 400 sets of molds ranging from Φ6mm to Φ2480mm. (For specific specifications, please refer to the core mold specification table). Special specifications will be negotiated separately.

إشعار الطلب:

1. All users, please try to apply the existing mandrel specifications, such as the cost and time of redo mandrel.

2. Because the production process has a period of time and the specifications of each user are different, please order in advance.


Performance parameter table of Class H epoxy fiberglass insulation cylinder

لا اسم المؤشر تفاصيل التخصص وحدة قيمة المؤشر
1 كثافة G / سم 3 1.9-2.0
2 Intensity of bending ما لا يقل عن MPA 320
3 Pressure resistance strength ما لا يقل عن MPA 200
4 قوة مضادة للقص ما لا يقل عن MPA 32
5 Medium Loss Factor (50Hz) No greater than 0.02
6 The dielectric constant 3 ~ 6
7 When the volume resistivity is normal ما لا يقل عن Qm 10X1011
After immersion 10X109
8 When the parallel layer moves toward the normal insulation resistance ما لا يقل عن Q 10X1011
After immersion 10X109
9 Surface voltage resistance

(Pressure-resistant lmin,30mm in the air)

KV 14
10 Vertical layer direction resistance voltage of 8> 3mm KV 20
11 Parallel layer-resistant voltage (25mm spacing) ما لا يقل عن KV 50
12 مقاومة العزل ما لا يقل عن MQ 5X104
13 Industrial frequency voltage resistance distance (by customer technology

المتطلبات)

ما لا يقل عن KV 80
14 المقاومة للحرارة ما لا يقل عن ° C 180
15 Meverage thermal deformation temperature ما لا يقل عن ° C 250