- 11
- Apr
Reference table of cable selection for metal melting furnace
Reference table of cable selection for metal melting furnace
| Cable ‘s
Nominal cross section ( Mm 2 ) |
Long-term allowable current ( A ) | ||||||||
| 1000 हर्ट्ज | 2500 हर्ट्ज | 8000 हर्ट्ज | |||||||
| Dual core | Three core | Four core | Dual core | Three core | Four core | Dual core | Three core | Four core | |
| 25 | 105 | 92 | – | 95 | 80 | – | 80 | 55 | – |
| 35 | 120 | 105 | – | 105 | 90 | – | 85 | 70 | – |
| 50 | 140 | 125 | 200 | 115 | 105 | 175 | 95 | 80 | 130 |
| 70 | 155 | 145 | 240 | 130 | 125 | 195 | 105 | 95 | 155 |
| 95 | 175 | 170 | 260 | 150 | 145 | 215 | 120 | 110 | 170 |
| 120 | 200 | 195 | 310 | 165 | 160 | 240 | 130 | 120 | 180 |
| 150 | 230 | 210 | 325 | 190 | 180 | 265 | 145 | 135 | 200 |
Note: The ambient temperature is 25 ℃ , and the cable temperature does not exceed 50 ℃ .