How to choose inverter thyristor for ಇಂಡಕ್ಷನ್ ಕರಗುವ ಕುಲುಮೆ?

1) ಇಂಡಕ್ಷನ್ ಕರಗುವ ಕುಲುಮೆಯ ಆಪರೇಟಿಂಗ್ ಆವರ್ತನ ಶ್ರೇಣಿಯ ಪ್ರಕಾರ ಆಯ್ಕೆಮಾಡಿ;

The frequency is 100HZ—500HZ and the selected turn-off time is 20µs-45µs KK type thyristor.

The frequency is 500HZ—1000HZ and the selected turn-off time is 18μs-25μs KK type thyristor.

The frequency is 1000HZ—2500HZ and the selected turn-off time is 12μs-18μs KK type thyristor.

KKG-type thyristor with a frequency of 2500HZ—4000HZ and a selected turn-off time of 10µs-14µs.

The frequency is 4000HZ—8000HZ, and the selected turn-off time is 6μs—9μs KA type SCR.

2) ಇಂಡಕ್ಷನ್ ಕರಗುವ ಕುಲುಮೆಯ ಔಟ್ಪುಟ್ ಶಕ್ತಿಯ ಪ್ರಕಾರ ಆಯ್ಕೆಮಾಡಿ;

According to the theoretical calculation of the parallel bridge inverter circuit, the current flowing through each thyristor is 0.455 times the total current. Considering that enough space is left, a thyristor with the same size as the rated current is usually selected.

300KW ಮತ್ತು 1400KW ನಡುವಿನ ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆಮಾಡಲಾದ ಪ್ರಸ್ತುತ 50A/100V ಥೈರಿಸ್ಟರ್. (380V ಹಂತದ ವೋಲ್ಟೇಜ್)

500KW-1400KW ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆ ಮಾಡಲಾದ ಪ್ರಸ್ತುತ 100A/250V ಥೈರಿಸ್ಟರ್. (380V ಹಂತದ ವೋಲ್ಟೇಜ್)

ಆಯ್ಕೆಮಾಡಿದ ಪ್ರಸ್ತುತ 800A/1600V ಥೈರಿಸ್ಟರ್ 350KW ನಿಂದ 400KW ವರೆಗಿನ ಶಕ್ತಿಯೊಂದಿಗೆ. (380V ಹಂತದ ವೋಲ್ಟೇಜ್)

1500KW ಮತ್ತು 1600KW ನಡುವಿನ ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆಮಾಡಲಾದ ಪ್ರಸ್ತುತ 500A/750V ಥೈರಿಸ್ಟರ್. (380V ಹಂತದ ವೋಲ್ಟೇಜ್)

1500KW ಮತ್ತು 2500KW ನಡುವಿನ ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆಮಾಡಲಾದ ಪ್ರಸ್ತುತ 800A/1000V ಥೈರಿಸ್ಟರ್. (660V ಹಂತದ ವೋಲ್ಟೇಜ್)

2000KW-2500KW ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆ ಮಾಡಲಾದ ಪ್ರಸ್ತುತ 1200A/1600V ಥೈರಿಸ್ಟರ್. (660V ಹಂತದ ವೋಲ್ಟೇಜ್)

2500KW ಮತ್ತು 3000KW ನಡುವಿನ ಶಕ್ತಿಯೊಂದಿಗೆ ಆಯ್ಕೆಮಾಡಲಾದ ಪ್ರಸ್ತುತ 1800A/2500V ಥೈರಿಸ್ಟರ್. (1250V ಹಂತದ ವೋಲ್ಟೇಜ್)