Jinsi ya kuchagua inverter thyristor kwa induction tanuru ya kuyeyuka?

How to choose inverter thyristor for tanuru ya kuyeyusha induction?

1) Chagua kulingana na safu ya mzunguko wa uendeshaji wa tanuru ya kuyeyuka ya induction;

The frequency is 100HZ—500HZ and the selected turn-off time is 20µs-45µs KK type thyristor.

The frequency is 500HZ—1000HZ and the selected turn-off time is 18μs-25μs KK type thyristor.

The frequency is 1000HZ—2500HZ and the selected turn-off time is 12μs-18μs KK type thyristor.

KKG-type thyristor with a frequency of 2500HZ—4000HZ and a selected turn-off time of 10µs-14µs.

The frequency is 4000HZ—8000HZ, and the selected turn-off time is 6μs—9μs KA type SCR.

2) Chagua kulingana na nguvu ya pato la tanuru ya kuyeyuka ya induction;

According to the theoretical calculation of the parallel bridge inverter circuit, the current flowing through each thyristor is 0.455 times the total current. Considering that enough space is left, a thyristor with the same size as the rated current is usually selected.

Thyristor ya sasa iliyochaguliwa ya 300A/1400V yenye nguvu kati ya 50KW na 100KW. (voltage ya awamu ya 380V)

Thyristor ya sasa iliyochaguliwa 500A/1400V yenye nguvu ya 100KW-250KW. (voltage ya awamu ya 380V)

Thyristor ya sasa ya 800A/1600V iliyochaguliwa yenye nguvu ya kuanzia 350KW hadi 400KW. (voltage ya awamu ya 380V)

Thyristor ya sasa iliyochaguliwa ya 1500A/1600V yenye nguvu kati ya 500KW na 750KW. (voltage ya awamu ya 380V)

Thyristor ya sasa iliyochaguliwa ya 1500A/2500V yenye nguvu kati ya 800KW na 1000KW. (voltage ya awamu ya 660V)

Thyristor ya sasa iliyochaguliwa 2000A/2500V yenye nguvu ya 1200KW-1600KW. (voltage ya awamu ya 660V)

Thyristor ya sasa iliyochaguliwa ya 2500A/3000V yenye nguvu kati ya 1800KW na 2500KW. (voltage ya awamu ya 1250V)